Standard Features
- tested to EN 14037
- modular system or perimeter system
- smooth flat faced unobstrusive design
- upto 460 w/m2 @ 55.5 dtK room (mwt - room temp)
- standard polyester finish RAL 9010 (20% gloss)
Optional Features
- can be customised to suit environment
- additional colour options
- aluminium or steal
- can be surfaced mounted
- can be wall mounted
water connections: 15mm OD EN1057:R250 Copper
weight : 37 kg/m2
Connection Possibilities
water: horizontal or vertical, same end or opposite.
Maintenance
The unit has no moving parts, and therefore maintenance requirement is limited to periodic cleaning of the surface of the panel.
Installation
Standard fixing arrangement from the structural soffit using M6 threaded rod or suitable wiring located at a maximum of 1.5m centres along the length of any run panel.
Other fixing methods are available dependent on project/application requirements.
For simplicity and flexibility we recommend that flexible stainless steel braided EPDM hoses are used to connect the Frengerwam panel.